Furnish and install where shown on the drawings, TEKNIHEAT type
AQUAZEST water/water heat pumps or equal. The appropriate series
AQ-C, AQ-H, or AG-D, will be selected where applicable.
HEAT PUMPS
All switches, control lights and monitoring points shall be installed
in one box in each machine.
The hot water temperature leaving the heat pump shall be constant and shll be controlled at 60 deg C with a fluctuation tolerance of plus/minus 1 deg C. The refrigerant shall be R22 (or R502) and the maximum condensing temperature of the compressor shall not exceed 55 deg C.
Heat pumps shall be coupled in such a way that they shall not stop and start intermittently and shall not run for less than 30min at a time.
Units shall be standard pre-wired, pre-charged, packaged units, ready for “plug in” applications.
A manual reset head pressure control shall be fitted in the box mentioned above.
Each heat pump shall be protected against loss of refrigerant and subsequent damage.
Each heat pump shall provide a 220V set of contacts in the event of any fault occurring internally.
In addition to the above specification, it may be required that each heat pump shall be internally wired via a terminal strip to provide:
Remote switching of individual compressor circuits (on/off)
Remote fault alarming of individual compressor circuits
Remote monitoring of units (hot & cold temperatures)
HEAT PUMP CONSTRUCTION
Unit casings shall be constructed in stainless steel. Condensate drip trays shall be made of fibreglass and condensers shall be constructed from copper or equal considering the operation conditions.
Ambient temperatures of up to 40 deg C shall not adversely affect heat pump operation.
An external bulkhead alarm light shall be fitted and shall be operated from the heat pump(s) as mentioned above.
Heat pump shall be of type AQUAZEST or equivalent. Preference shall be given to locally manufactured units where local companies can also supply expertise and competent service.
GENERAL
Condensate pipes shall be suitably insulated so as no to allow moisture formation. Plastic piping will be permissible.
PREFERENTIAL TREATMENT FOR EQUIPMENT OFFERED
Preference will be given to those tenderes who already have a successful track record of locally-produced units running under local conditions.
WARRANTY
Tekniheat warrants this equipment to be free from defects in material and workmanship for a
period of 12 months from plant commissioning or 15 months from date of shipment,
whichever is the shorter period. Any units or parts proving defective within this period will be
repaired or replaced at our option when returned to our factory transportation charges
pre-paid. Tekniheat will not be responsible for any installation or removal costs.
|